Viessmann Boiler: Bus termination and Time Master checks
Bus termination and Time Master checks on a Viessmann boiler: Only one bus termination resistor and only one Time Master may be used in the system. Incorrect settings can cause malfunctions.
Applies to: Versatronik 200 system with multiple controllers and bus
How to fix bus termination and time master checks: step by step
- Confirm only one controller (HG or cascade controller) has BUS Termination set to On. Set it to Off if a CoCo is installed.
- Confirm only one controller has Time Master set to On.
- Check that heating circuit numbers (BUS ID) are unique; replacement controllers must match the old numbers.
If the unit shows an error code, look it up: Viessmann Boiler codes
More commissioning tips for boiler
Source: Versatronik 200 installation and operating manual, p. 137. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.