Viessmann Boiler: Log in to gateway configuration pages
Log in to gateway configuration pages on a Viessmann boiler: The gateway has a built-in web configuration page. Default login is admin / admin. You can rename the password on the Change Password screen.
Applies to: Versatronik 585 VI/BACIP
How to fix log in to gateway configuration pages: step by step
- Connect your computer directly to the gateway BACnet port with no other devices attached.
- Set the computer to automatic IP (DHCP), or set its IP address to 192.168.88.90 with subnet mask 255.255.255.0.
- Power-cycle the gateway (power off, then on).
- Open a browser and go to http://192.168.88.89/admin.
- Log in with the default user name and password admin (no quotes), or with your changed password.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
More access & passwords tips for boiler
Source: Versatronik 585 and 585D BACnet IP gateway manual, p. 13. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.