Rheem Furnace: Condensate vent tube height options
Condensate vent tube height options on a Rheem furnace: Two options exist for the condensate vent riser height. The choice decides whether the furnace keeps running when the drain is blocked.
Applies to: Condensate vent riser on all 96V furnaces
How to fix condensate vent tube height options: step by step
- Option A: put the top of the vent tube below the lower condensate water level sensor. The furnace keeps running when the drain is blocked, but water spills from the tube. Make sure there is a way to handle that water.
- Option B: put the top of the vent tube above the lower condensate water level sensor. A blocked drain shuts the furnace down and no water spills.
- Choose the option based on the customer's acceptance of overflow versus loss of heat.
If the unit shows an error code, look it up: Rheem Furnace codes
Models
(-)96V060(-)96V070(-)96V085(-)96V10096VA06096VA07096VA08596VA100
More commissioning tips for furnace
Source: 96V series installation instructions, p. 67. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.