Updated · by Aurora Star Tech Inc.

This page follows a heating cycle in a Trane AUH1B furnace, from the thermostat click to the moment the warm air stops. It helps explain why there is a short wait after you ask for heat.

Homeowner with a furnace problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

How the Trane furnace works: Heating sequence of operation

What this is. This page follows a heating cycle in a Trane AUH1B furnace, from the thermostat click to the moment the warm air stops. It helps explain why there is a short wait after you ask for heat.

What happens, in order. When the thermostat calls for heat, the control checks itself and confirms that the pressure switch is open and the safety limit switches are closed. The induced draft blower starts, and when it reaches speed the pressure switch closes. The ignitor then warms up for about 20 seconds, the gas valve opens, and the burners light. The flame sensor has 4 seconds to prove there is a flame. After the fan-on delay, the main blower starts: around 45 seconds on upflow and horizontal furnaces, or 10 seconds on downflow ones. When the room is warm, the gas valve closes, the flame goes out and the draft blower stops. The main blower runs a bit longer, for the fan-off period, which is 100 seconds from the factory and can be set to 60, 140 or 180.

What is normal. A delay before warm air starts, soft clicking, and the main fan continuing after the burners shut off.

Codes you may see. The furnace light may flash two or three times in a repeating pattern. These flash codes tell a technician what the control noticed, so jot down the pattern.

Safe checks. Replace the filter, open the registers, check the thermostat and breaker, and clear snow from outside vent pipes.

When to call a technician. If a flash code returns after a single power reset or the furnace goes cold. Aurora Star Tech services Trane furnaces across Vaughan, Toronto and the GTA.

Key times at a glance

WhatHow long or how much
Ignitor warm-up before gas valve opensapprox. 20 s
Flame sensor ignition trial4 s
Blower ON delay (upflow/horizontal)approx. 45 s
Blower ON delay (downflow)10 s
Fan-off period60, 100, 140 or 180 s (factory 100 s)

Applies to: AUH1B furnaces

Error codes linked to this step

Trane code 2 FlashesTrane code 3 Flashes

Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

Questions about the Trane furnace

What is the Heating sequence of operation on a Trane furnace?

This page follows a heating cycle in a Trane AUH1B furnace, from the thermostat click to the moment the warm air stops. It helps explain why there is a short wait after you ask for heat.

Is it normal for my Trane furnace to do this?

A delay before warm air starts, soft clicking, and the main fan continuing after the burners shut off.

Who can service my Trane furnace near me?

Aurora Star Tech Inc. repairs and services Trane furnaces in Vaughan, Toronto and across the GTA. Call (647) 657-2977 or book a service call online.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.