Updated · by Aurora Star Tech Inc.

Trane S8B1, S8X1 and S8X2 are 80 percent efficient gas furnaces. This page follows the first stage of heating, step by step, so each click and hum makes sense.

Homeowner with a furnace problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

How the Trane furnace works: First-stage gas heating

What this is. Trane S8B1, S8X1 and S8X2 are 80 percent efficient gas furnaces. This page follows the first stage of heating, step by step, so each click and hum makes sense.

What happens, in order. When the thermostat asks for heat, the furnace display shows Xt (or Xt1 on the two-stage S8X2). The control first checks that its safety switches are closed and that the pressure switch is still open. The inducer, a small fan that pulls air through the furnace, then starts; on the S8X2 it begins on high for about 6 seconds before settling to low. The pressure switch must close to prove air is moving, and the furnace allows 60 seconds for that. If it does not, the display shows e3.1 and the inducer runs on high to try again. The igniter then glows for about 17 seconds, the first-stage gas valve opens and a flame must be proven within 4 seconds. The blower then starts at first-stage speed after its heating delay.

When heating ends. The gas valve closes, the inducer runs about 5 more seconds to clear the fumes and the blower runs for the off time set in the control menu. The display returns to IDL, meaning idle. Any air cleaner turns on about 2 seconds after the blower, and a humidifier about 1 second after.

What is normal. Humming, a short wait with no heat, and the blower running after the burners stop.

Safe checks. Replace a dirty filter, make sure the furnace door is on, the power switch is on, and the exhaust and intake pipes outside are clear of snow and nests.

When to call a technician. Code e3.1, repeated shutdowns or any gas smell (leave and call from outside) means calling Aurora Star Tech.

Key times at a glance

WhatHow long or how much
Ignitor warm-upabout 17 s
Flame prove time4 s
Pressure switch 1 prove time60 s
Post-purgeabout 5 s
Typical flame current0.75 to 3.0 uA (read as 0.75 to 3 VDC at the FP pads)
EAC relay delayabout 2 s after blower starts
HUM relay delayabout 1 s after blower starts

Applies to: S8B1, S8X1 and S8X2 80 percent furnaces

Error codes linked to this step

Trane code E3.1Trane code IdL

Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

Questions about the Trane furnace

What is the First-stage gas heating on a Trane furnace?

Trane S8B1, S8X1 and S8X2 are 80 percent efficient gas furnaces. This page follows the first stage of heating, step by step, so each click and hum makes sense.

Is it normal for my Trane furnace to do this?

Humming, a short wait with no heat, and the blower running after the burners stop.

Who can service my Trane furnace near me?

Aurora Star Tech Inc. repairs and services Trane furnaces in Vaughan, Toronto and across the GTA. Call (647) 657-2977 or book a service call online.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.

Emergency Furnace Repair

647-657-2977