Rinnai furnace: Ignition failure and flame loss retry
Sometimes a furnace simply fails to light on the first attempt. The Rinnai EX DT room furnace is built to wait and try again rather than keep forcing it, and this page explains what that looks like.
How the Rinnai furnace works: Ignition failure and flame loss retry
What this is. Sometimes a furnace simply fails to light on the first attempt. The Rinnai EX DT room furnace is built to wait and try again rather than keep forcing it, and this page explains what that looks like.
What happens, in order. If the burner does not light, the furnace stops and waits one full hour before trying again. While it waits, the display shows fault code 11, which means ignition failure. If the next try works, the code clears by itself. If it fails, the code stays and another attempt follows an hour later. The same one-hour wait and code 11 apply if the flame goes out during the first 15 to 18 seconds, the forced combustion period, after start-up.
A different case. If the flame goes out later, while the thermostat is running the burner, the furnace tries to relight right away and no code appears. This ignition code is not saved in the fault history, so note when you saw it.
What is normal. An occasional single failed light, especially after the furnace has sat unused for weeks, followed by a quick relight. Code 11 appearing for a time and then disappearing on its own is the furnace working through its retries.
Safe checks. Make sure the outdoor vent and air intake are clear of snow, leaves and ice, the gas supply to the home is on, and the thermostat is calling for heat. You may switch the furnace off and on once. Do not open the furnace or touch gas parts.
When to call a technician. If code 11 stays on for several hours, comes back every day, or you smell gas, leave the house and call from outside. Aurora Star Tech services room furnaces in Vaughan, Toronto and the GTA.
Key times at a glance
| What | How long or how much |
|---|---|
| Retry delay after ignition failure | 1 h |
| Forced combustion period | about 15 to 18 s |
Applies to: Rinnai EX08DT, EX11DT, EX17DT, EX22DT direct-vent room furnaces
Questions about the Rinnai furnace
What is the Ignition failure and flame loss retry on a Rinnai furnace?
Sometimes a furnace simply fails to light on the first attempt. The Rinnai EX DT room furnace is built to wait and try again rather than keep forcing it, and this page explains what that looks like.
Is it normal for my Rinnai furnace to do this?
An occasional single failed light, especially after the furnace has sat unused for weeks, followed by a quick relight. Code 11 appearing for a time and then disappearing on its own is the furnace working through its retries.
Who can service my Rinnai furnace near me?
Aurora Star Tech Inc. repairs and services Rinnai furnaces in Vaughan, Toronto and across the GTA. Call (647) 657-2977 or book a service call online.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.