Midea furnace: Low fire heat call (W1 only)

Updated · by Aurora Star Tech Inc.

Midea's A2L 96 percent two-stage gas furnace (BGH96M) can heat gently or at full output. This page covers the gentle "low fire" start, which runs when the thermostat asks for the first stage of heat only.

Homeowner with a furnace problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

How the Midea furnace works: Low fire heat call (W1 only)

What this is. Midea's A2L 96 percent two-stage gas furnace (BGH96M) can heat gently or at full output. This page covers the gentle "low fire" start, which runs when the thermostat asks for the first stage of heat only.

What happens, in order. The thermostat calls and the inducer fan, which clears the burner area, starts on high speed. After about 15 seconds the safety air switch closes and confirms airflow. The inducer then drops to low speed and the igniter glows for about 17 seconds to preheat. The gas valve opens and the burners light, and the igniter turns off 3 seconds later. The main blower begins 30 seconds after that and the furnace carries on at low fire.

When the call ends. Once the thermostat is satisfied and the flame is gone, the inducer runs a 15-second post-purge to clear leftover gases. The blower then keeps running to deliver the last of the heat, for a delay that is normally 180 seconds, though a technician can set it differently.

What is normal. About a minute from thermostat call to warm air, a rising whirr from the inducer, a click and glow from the igniter, quieter and steadier operation on low fire, and a blower that runs for a few minutes after the burners go out.

Safe checks. Check the thermostat setting, furnace switch and breaker, replace a dirty filter and clear snow or debris from the outdoor vent pipes. One power reset, off for ten seconds, is fine.

When to call a technician. Codes such as E1 through E8, FL or Pr on the display, no warm air, or a smell of gas (leave the house and call from outside) call for help. Aurora Star Tech services furnaces across the GTA.

Key times at a glance

WhatHow long or how much
Inducer high speed / switch proving15 s
Igniter preheat17 s
Igniter off after valve opens3 s
Blower on delay30 s
Post-purge15 s
Heat fan off delay (default)180 s

Applies to: Midea A2L 96 percent gas furnace

Error codes linked to this step

Midea code E1

Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

Questions about the Midea furnace

What is the Low fire heat call (W1 only) on a Midea furnace?

Midea's A2L 96 percent two-stage gas furnace (BGH96M) can heat gently or at full output. This page covers the gentle "low fire" start, which runs when the thermostat asks for the first stage of heat only.

Is it normal for my Midea furnace to do this?

About a minute from thermostat call to warm air, a rising whirr from the inducer, a click and glow from the igniter, quieter and steadier operation on low fire, and a blower that runs for a few minutes after the burners go out.

Who can service my Midea furnace near me?

Aurora Star Tech Inc. repairs and services Midea furnaces in Vaughan, Toronto and across the GTA. Call (647) 657-2977 or book a service call online.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.