Lennox furnace: Single-stage furnace gas heating cycle
Lennox EL195UHNE and ML180UHEK single-stage gas furnaces follow a strict safety checklist every time your thermostat calls for heat. Knowing the order makes the clicks, hum and brief waits easier to understand.
How the Lennox furnace works: Single-stage furnace gas heating cycle
What this is. Lennox EL195UHNE and ML180UHEK single-stage gas furnaces follow a strict safety checklist every time your thermostat calls for heat. Knowing the order makes the clicks, hum and brief waits easier to understand.
What happens, in order. The control first runs a self-check and confirms that its safety limit switches are closed and that the airflow pressure switch is open. If that switch is already closed, the furnace will not start. The inducer fan, which draws air through the furnace, starts next. When airflow is confirmed, a 15-second purge follows. The igniter then warms for 20 seconds, the gas valve opens a moment before that ends, and a 4-second window begins in which flame must appear. Once flame is proven, the valve stays open, and the main blower starts 30 seconds later. When the thermostat is satisfied, the gas closes, the inducer runs 5 more seconds, and the blower keeps going for a cool-down of 90 seconds on the EL195 or 120 seconds on the ML180.
Protections. If airflow is not confirmed within 2.5 minutes, the furnace waits 5 minutes and tries again. An overheated limit shuts the gas and lets the blower run to cool things down, and an open rollout switch shuts the gas and holds the furnace until it is reset.
What is normal. Humming, clicking, a short wait, and a blower running for a minute or two after the flame goes out.
Safe checks. Replace the filter, check the thermostat and breaker and clear outdoor vent pipes of snow. One power reset is fine.
When to call. A flashing light that returns, repeated shutdowns, or any gas smell, in which case leave and call from outside. Aurora Star Tech can help.
Key times at a glance
| What | How long or how much |
|---|---|
| Pre-purge | 15 s |
| Ignitor warm-up | 20 s |
| Gas valve opens | 19 s into warm-up |
| Trial for ignition | 4 s |
| Ignitor on during trial | first 3 s |
| Pressure switch prove time | 2.5 min, then 5 min wait |
| Blower on delay | 30 s after flame (not adjustable) |
| Post-purge | 5 s |
| Blower off delay EL195 | 90 s factory, jumper adjustable |
| Blower off delay ML180 | 120 s factory, 2-position dip switch, 4 choices |
| Low voltage lockout | below 70 V stops, resumes above 75 V (EL195) |
Applies to: EL195UHNE, ML180UHEK gas furnaces with single-stage integrated control
Questions about the Lennox furnace
What is the Single-stage furnace gas heating cycle on a Lennox furnace?
Lennox EL195UHNE and ML180UHEK single-stage gas furnaces follow a strict safety checklist every time your thermostat calls for heat. Knowing the order makes the clicks, hum and brief waits easier to understand.
Is it normal for my Lennox furnace to do this?
Humming, clicking, a short wait, and a blower running for a minute or two after the flame goes out.
Who can service my Lennox furnace near me?
Aurora Star Tech Inc. repairs and services Lennox furnaces in Vaughan, Toronto and across the GTA. Call (647) 657-2977 or book a service call online.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.