Goodman-Amana-Daikin furnace: Gas heat call, first and second stage
A Goodman, Amana or Daikin two-stage 96 percent furnace with a digital display follows a careful routine each time the thermostat asks for heat. This page walks through that routine.
How the Goodman-Amana-Daikin furnace works: Gas heat call, first and second stage
What this is. A Goodman, Amana or Daikin two-stage 96 percent furnace with a digital display follows a careful routine each time the thermostat asks for heat. This page walks through that routine.
What happens, in order. The control first runs a self-check of its safety switches. The inducer, a small fan that pulls air through the furnace, starts and clears the chamber. The igniter warms up, the gas valve opens for about 4 seconds to catch the flame, and the igniter shuts off as soon as the flame is sensed. About 30 seconds later the main blower starts pushing warm air into your home. With a single-stage thermostat, the furnace moves to second stage after a fixed timer or in an automatic mode chosen by the installer. A second-stage call speeds up the inducer and blower and opens the high-fire gas stage. When the thermostat is satisfied, the gas closes, the inducer runs 15 more seconds, and the blower runs on for a cool-down, 90 seconds by default.
If there is no flame. The control tries again, up to three times in one call, then locks out and shows E0. It resets itself after one hour.
What is normal. A wait with no heat after the thermostat clicks, fan and clicking sounds, and the blower running a minute or two after the flame stops.
Safe checks. Replace a dirty filter, make sure the furnace door is closed, check the thermostat and breaker, and clear snow from the outside vent pipes. You may turn power off for ten seconds and on again once. If you smell gas, leave and call from outside.
When to call a technician. The display shows E0, E1, E2 or E8, or heat keeps stopping. Aurora Star Tech can help.
Key times at a glance
| What | How long or how much |
|---|---|
| Trial for ignition | 4 s |
| Blower on delay | 30 s |
| Post-purge | 15 s |
| Blower off delay | 90 s default, 30 to 180 s |
| Ignition tries per call | 3 (retries), then lockout |
| Lockout auto reset | 1 hour |
Applies to: Goodman GC9C96, GM9C96, AC9C96, AM9C96; Daikin DR96TN, DD96TN; Goodman/Amana GM9S96 family (single-stage models skip the second-stage steps)
Error codes linked to this step
Goodman code E0Goodman code E1Goodman code E2Goodman code E8
Questions about the Goodman-Amana-Daikin furnace
What is the Gas heat call, first and second stage on a Goodman-Amana-Daikin furnace?
A Goodman, Amana or Daikin two-stage 96 percent furnace with a digital display follows a careful routine each time the thermostat asks for heat. This page walks through that routine.
Is it normal for my Goodman-Amana-Daikin furnace to do this?
A wait with no heat after the thermostat clicks, fan and clicking sounds, and the blower running a minute or two after the flame stops.
Who can service my Goodman-Amana-Daikin furnace near me?
Aurora Star Tech Inc. repairs and services Goodman-Amana-Daikin furnaces in Vaughan, Toronto and across the GTA. Call (647) 657-2977 or book a service call online.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.