Updated · by Aurora Star Tech Inc.

Newer Goodman air handlers that use R-32 refrigerant have a small leak sensor, called RDS, next to the indoor coil. If it detects refrigerant, the system switches into a protective mode. This page explains what you will see and hear.

Homeowner with a air handler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

How the Goodman-Amana-Daikin air handler works: R-32 leak detection response and test

What this is. Newer Goodman air handlers that use R-32 refrigerant have a small leak sensor, called RDS, next to the indoor coil. If it detects refrigerant, the system switches into a protective mode. This page explains what you will see and hear.

What happens, in order. When the sensor detects R-32, the system drops the thermostat's call, switches off any electric heat and runs the blower to circulate air through the space. A red light on the control board flashes quickly while the alarm is active. When the sensor reads clear again, the unit stays in this protective mode for another 5 minutes, with the light on steady, before returning to normal. The unit must stay powered during an alarm, so please do not shut it off or open it unless a technician tells you to. Technicians can also trigger a 5-minute test of the sensor by pressing the board button twice, and ending it with a single press.

What is normal. A slow, steady flash, about 2 seconds on and 2 off, in everyday operation. Other flash patterns of 2, 3 or 4 flashes followed by a pause point to a board, sensor communication or sensor fault, not a leak, but they also need a technician.

Safe checks. If you smell or hear anything unusual and the air handler is in a closed space, open windows and doors for ventilation, and keep sources of ignition away. Do not open the unit.

When to call a technician. Any alarm that repeats, a rapidly flashing red light, a system that runs only the fan, or any fault pattern. Call Aurora Star Tech for a prompt service visit.

Key times at a glance

WhatHow long or how much
Normal operation LEDslow flash, 2 s on / 2 s off
Mitigation hold after alarm5 min
Test run5 min max
Board internal fault2 flashes then 5 s off
Sensor communication fault3 flashes then 5 s off
Sensor fault4 flashes then 5 s off

Applies to: Goodman R-32 GLXS / GLZS / ALXS / ALZS and AMST / AWST air handlers

Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

Questions about the Goodman-Amana-Daikin air handler

What is the R-32 leak detection response and test on a Goodman-Amana-Daikin air handler?

Newer Goodman air handlers that use R-32 refrigerant have a small leak sensor, called RDS, next to the indoor coil. If it detects refrigerant, the system switches into a protective mode. This page explains what you will see and hear.

Is it normal for my Goodman-Amana-Daikin air handler to do this?

A slow, steady flash, about 2 seconds on and 2 off, in everyday operation. Other flash patterns of 2, 3 or 4 flashes followed by a pause point to a board, sensor communication or sensor fault, not a leak, but they also need a technician.

Who can service my Goodman-Amana-Daikin air handler near me?

Aurora Star Tech Inc. repairs and services Goodman-Amana-Daikin air handlers in Vaughan, Toronto and across the GTA. Call (647) 657-2977 or book a service call online.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.