Goodman furnace: Heating mode sequence of operation

Updated · by Aurora Star Tech Inc.

Goodman ACVC96, AMVC96, GCVC96 and GMVC96 furnaces heat in two stages, low and high. This page walks through a whole heating cycle so the sounds make sense.

Homeowner with a furnace problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

How the Goodman furnace works: Heating mode sequence of operation

What this is. Goodman ACVC96, AMVC96, GCVC96 and GMVC96 furnaces heat in two stages, low and high. This page walks through a whole heating cycle so the sounds make sense.

What happens, in order. The thermostat asks for heat and the furnace checks its safety circuits. The inducer fan runs on high for a 15-second pre-purge, then drops to low. Once airflow is proven, the igniter warms up, the gas valve opens and a flame is established. The gas valve stays open only while the flame is detected. The control picks low or high stage by its own logic, though the first call after a power interruption is always high. The main blower begins after the fan-on delay, 30 seconds by default, and ramps up gently. If the stage steps up, everything moves to high right away. Stepping down, the burner drops to low immediately, but the blower stays on high for another 30 seconds before settling to low. When the call ends, the flame goes out and the inducer clears the chamber for 15 seconds. The blower continues for the fan-off delay, 90 seconds by default, finishing on low speed after 30 seconds of high if the last call was high.

What is normal. A pause before warm air, the fan speed changing mid-cycle, and the blower keeping going after the burners stop.

Safe checks. Replace the filter, open the registers, check the thermostat and keep vents outside clear.

When to call a technician. If the furnace cycles on and off, shows a code, or the house stays cool. If you smell gas, leave and call from outside. Aurora Star Tech can help.

Key times at a glance

WhatHow long or how much
Induced draft prepurge (high speed)15 seconds
Induced draft post purge15 seconds
Circulator high heat speed before switching to low heat30 seconds
Gas heat fan on delay (default)30 seconds
Gas heat fan off delay (default)90 seconds

Applies to: All 34.5in chassis furnaces

Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

Questions about the Goodman furnace

What is the Heating mode sequence of operation on a Goodman furnace?

Goodman ACVC96, AMVC96, GCVC96 and GMVC96 furnaces heat in two stages, low and high. This page walks through a whole heating cycle so the sounds make sense.

Is it normal for my Goodman furnace to do this?

A pause before warm air, the fan speed changing mid-cycle, and the blower keeping going after the burners stop.

Who can service my Goodman furnace near me?

Aurora Star Tech Inc. repairs and services Goodman furnaces in Vaughan, Toronto and across the GTA. Call (647) 657-2977 or book a service call online.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.

Emergency Furnace Repair

647-657-2977