Carrier heat pump: Single-stage communicating heat pump: time delays and operating functions
A Carrier Infinity single-stage heat pump paired with a communicating control has a handful of built-in pauses and protective timings. This page lists them so a short wait does not look like a fault.
How the Carrier heat pump works: Single-stage communicating heat pump: time delays and operating functions
What this is. A Carrier Infinity single-stage heat pump paired with a communicating control has a handful of built-in pauses and protective timings. This page lists them so a short wait does not look like a fault.
What happens, in order. On a cooling call, the outdoor fan, reversing valve and compressor come on, and when satisfied the compressor and fan stop while the valve stays in cooling until the next heating call or a power loss. On a heating call, the fan and compressor start with the valve off. The outdoor fan runs whenever the compressor does, with exceptions like defrost. After cooling in 100 F weather, the fan runs a minute longer. Starting is held for 5 minutes after power loss or a brown-out. After defrost, the backup heat stays on for 15 seconds more and the outdoor fan waits 20 seconds. In cold weather below 65 F, the crankcase heater warms the compressor during the off cycle. The system returns to standby 2 minutes after the last valid communication.
What is normal. A five minute wait before the outdoor unit starts, a fan running briefly after cooling, and a quiet unit with a warm compressor.
Safe checks. Wait it out, then check the thermostat, breakers and filter, and clear leaves and snow from the outdoor unit.
When to call. If the unit never starts or the thermostat reports communication trouble, call Aurora Star Tech.
Key times at a glance
| What | How long or how much |
|---|---|
| Start delay for cooling or heating | 5 min |
| Compressor recycle after brown-out | 5 min |
| Return to standby after last valid communication | 2 min |
| Fan run-on in cooling at 100 F+ outdoor | 1 min |
| W2 off delay after defrost | 15 s |
| Fan on delay after defrost | 20 s |
| Compressor delays with Quiet Shift-2 | 70 s and 60 s |
Applies to: Carrier / Bryant / Payne split heat pumps with HK32EA defrost control boards (Performance Series and Comfort Series)
Questions about the Carrier heat pump
What is the Single-stage communicating heat pump: time delays and operating functions on a Carrier heat pump?
A Carrier Infinity single-stage heat pump paired with a communicating control has a handful of built-in pauses and protective timings. This page lists them so a short wait does not look like a fault.
Is it normal for my Carrier heat pump to do this?
A five minute wait before the outdoor unit starts, a fan running briefly after cooling, and a quiet unit with a warm compressor.
Who can service my Carrier heat pump near me?
Aurora Star Tech Inc. repairs and services Carrier heat pumps in Vaughan, Toronto and across the GTA. Call (647) 657-2977 or book a service call online.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.