Bosch heat pump: Demand defrost
On a cold day the outdoor coil of your Bosch IDS heat pump slowly gathers frost, the way a freezer does. The unit is designed to notice this on its own and melt the ice away, and this page explains how it decides, what you will see and how it finishes.
How the Bosch heat pump works: Demand defrost
What this is. On a cold day the outdoor coil of your Bosch IDS heat pump slowly gathers frost, the way a freezer does. The unit is designed to notice this on its own and melt the ice away, and this page explains how it decides, what you will see and how it finishes.
What happens, in order. The unit compares the temperature of its outdoor coil with the outside air. If the gap stays wide enough for 3 minutes, frost is assumed and a defrost begins. The gap it looks for depends on the weather: 18 degrees F when the air is 39 F or warmer, 16 degrees at 30 F or warmer, and 14 degrees at 19 F or warmer. In very cold air it also counts running time, starting a defrost after 80 minutes of compressor work. Run-time backups exist as well: after 4 hours of heating when the air is below 23 F, or 2 hours in the mild-cold range. A low pressure reading can start one too. While it defrosts, the outdoor display shows "dF". It ends once the coil warms to about 64 F for a minute, or after 8 minutes, whichever is first.
What is normal. White vapour rising off the unit, dripping or running water, a brief whoosh as the system changes direction, and slightly cooler air from your vents for a few minutes.
Safe checks. Keep snow, ice and leaves cleared from around the outdoor unit and confirm the thermostat is set to Heat with a clean filter indoors.
When to call a technician. If the unit stays buried in ice, seems to defrost nonstop, or the house will not warm up, Aurora Star Tech can inspect it for you across Vaughan, Toronto and the GTA.
Key times at a glance
| What | How long or how much |
|---|---|
| Delta T, air 39F or above | 18F |
| Delta T, air 30F or above | 16F |
| Delta T, air 19F or above | 14F |
| Delta T hold time | 3 min |
| Run time, air below 19F and coil below 9F | 80 min |
| Minimum run time, air below 23F | 4 h |
| Defrost end | Coil 64F for 1 min, or 8 min max |
| Low-pressure defrost trigger | Below 82F saturation for 20 min |
Applies to: Bosch IDS inverter heat pump condensing units
Error codes linked to this step
Questions about the Bosch heat pump
What is the Demand defrost on a Bosch heat pump?
On a cold day the outdoor coil of your Bosch IDS heat pump slowly gathers frost, the way a freezer does. The unit is designed to notice this on its own and melt the ice away, and this page explains how it decides, what you will see and how it finishes.
Is it normal for my Bosch heat pump to do this?
White vapour rising off the unit, dripping or running water, a brief whoosh as the system changes direction, and slightly cooler air from your vents for a few minutes.
Who can service my Bosch heat pump near me?
Aurora Star Tech Inc. repairs and services Bosch heat pumps in Vaughan, Toronto and across the GTA. Call (647) 657-2977 or book a service call online.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.