Bosch air handler: Blower control: anti-cold-air delay and heating fan delay
Your Bosch IDS air handler does not simply blow the moment heat is requested. It controls the blower speed and start time so you are not hit with cold air. This page explains how that works.
How the Bosch air handler works: Blower control: anti-cold-air delay and heating fan delay
What this is. Your Bosch IDS air handler does not simply blow the moment heat is requested. It controls the blower speed and start time so you are not hit with cold air. This page explains how that works.
What happens, in order. The thermostat sets the speed. A stage 1 call gives low speed, stage 2 gives high speed, a fan-only call gives low speed, and electric heat runs the blower on high. In one setup option the air handler holds the blower off until its indoor coil has warmed up, from below about 82 F to about 89.6 F. That wait ends if the heater kit starts, the call ends, or after 15 minutes. If the conditions linger for 2 minutes, the blower starts at first-stage speed anyway. In the other setup option the blower simply starts after a fixed 90 seconds.
What is normal. A minute or more of quiet after the thermostat calls for heat, then warm air building up. The wait avoids a cold draft on your skin.
Safe checks. Make sure the thermostat is set to Heat, replace a dirty filter and keep supply vents and return grilles open.
When to call. If the blower never starts, or runs only on high, Aurora Star Tech can check the settings and wiring. These options are set by the installer, so please do not adjust anything inside the unit yourself.
Key times at a glance
| What | How long or how much |
|---|---|
| Fan delay (SW6-3 OFF) | 90 s |
| Anti-cold-air entry coil temp | Below 82.4F |
| Anti-cold-air exit coil temp | 89.6F or higher |
| Anti-cold-air maximum | 15 min |
| Forced first stage after | 120 s |
Applies to: Bosch IDS Premium air handlers
Questions about the Bosch air handler
What is the Blower control: anti-cold-air delay and heating fan delay on a Bosch air handler?
Your Bosch IDS air handler does not simply blow the moment heat is requested. It controls the blower speed and start time so you are not hit with cold air. This page explains how that works.
Is it normal for my Bosch air handler to do this?
A minute or more of quiet after the thermostat calls for heat, then warm air building up. The wait avoids a cold draft on your skin.
Who can service my Bosch air handler near me?
Aurora Star Tech Inc. repairs and services Bosch air handlers in Vaughan, Toronto and across the GTA. Call (647) 657-2977 or book a service call online.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.