Trane Furnace: Roof venting
Roof venting on a Trane furnace: Roof vent. Keep a set height over snow. Seal the roof penetration. Leaks here mean wet ceilings. Too tall and the pipe gets exposed to wind and frost. Too short and snow buries it. Canada needs more snow clearance than the US.
Applies to: Vertical roof venting
Common causes of roof venting
- Vent too low, buried by snow
- Vent too tall above the roof, unsupported in wind
- Unsealed roof penetration leaking
- Combustion air inlet not meeting the dimensions in the figure
- Rain cap ribs left in place restricting flow
How to fix roof venting: step by step
- Keep at least 12 in clearance above the highest expected snow level (18 in in Canada).
- Keep the vent no more than 24 in above the roof.
- Seal a 2 in PVC vent through the roof using a 2 in electrical conduit flashing. Lubricate the flexible seal before pushing the pipe through.
- Use a roof flashing boot (field supplied) and a support (field supplied) as needed.
- Use the combustion air inlet with the roof vent, meeting the dimensions in the venting figure.
- Remove the ribs from the cap where a rain cap is used.
- Check for leaks in the attic after the first heavy rain.
If the unit shows an error code, look it up: Trane Furnace codes
Models
UH1B040A9241AUH1B060A9361AUH1B080A9421BUH1C080A9601AUH1C100A9481AUH1D100A9601AUH1D120A9601A
Source: Trane installer's guide, p. 23. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.