Trane Furnace: Measure manifold pressure from the burner box
Measure manifold pressure from the burner box on a Trane furnace: Manifold pressure on this Trane has to be referenced to the burner box, not read against room air at the valve outlet. Gas work, so a licensed technician should set it. Get the reference right or the reading means nothing, and a bad reading leads to overfiring or sooting.
Applies to: Manifold pressure checks
Common causes of measure manifold pressure from the burner box
- Manifold pressure read without the burner box reference
- Tap plug not sealed after adjusting, leaving a gas leak
- Tee or tubing connection leaking at the reference line
How to fix measure manifold pressure from the burner box: step by step
- Install a field-supplied tee in the tubing between the burner box tube and the gas valve.
- Keep the regular gas valve outlet pressure tap in use as well.
- Check manifold pressure at the burner box reference.
- After adjusting, replace the manifold pressure tap threaded plug.
- Leak check the plug and tubing connections with leak detector solution.
If the unit shows an error code, look it up: Trane Furnace codes
Source: Trane 18-CD29D1-11 installer's guide, p. 33. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.