Trane Furnace: Limit switch check during startup
Limit switch check during startup on a Trane furnace: The high limit has to open and shut the burners off at the rated outlet temperature. This is an installer's check at startup, and I always do it, because a limit that does not trip is the difference between a nuisance call and a fire. What I usually find on a bad one is that it simply never opens, and the furnace keeps firing while the plenum gets hot. Stay with the furnace the whole test and be ready to shut it down by hand.
Applies to: All furnaces at initial startup
Common causes of limit switch check during startup
- Faulty limit switch if burners keep running and overheating is evident
- Limit sensor not seeing heat because of mounting or position
- Blower or airflow problem causing the limit to trip early instead
- Wiring fault in the limit circuit
How to fix limit switch check during startup: step by step
- Set the thermostat above the setpoint to bring on the gas valve.
- Restrict airflow by blocking the return air. Disconnecting the indoor blower can trip the inducer limit.
- Watch for the burners to shut off when outlet temperature reaches the rating plate maximum.
- If the burners do not shut off and overheating occurs, shut the furnace off manually at once and replace the limit switch.
- Check continuity across the limit with a meter once it cools to confirm it recloses.
- Remove the paper or cardboard from the return air inlet after the test.
- Never leave a limit bypassed or a faulty limit in service.
If the unit shows an error code, look it up: Trane Furnace codes
Source: Trane 18-CD29D1-11 installer's guide, p. 40. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.