Trane Furnace: Limit switch check at startup
Limit switch check at startup on a Trane furnace: Verify the high limit shuts off burners when the furnace overheats. Installer check at startup. Watch it the whole time. Stay at the furnace and shut it off by hand if it does not trip.
Applies to: AUH1B furnaces
Common causes of limit switch check at startup
- Limit switch failed to open
- Limit not seeing outlet air temperature properly
- Wiring problem in the limit circuit
- Inducer limit tripping from blower disconnection instead
How to fix limit switch check at startup: step by step
- Set thermostat above room temperature to call for heat.
- Restrict airflow by blocking the return air. Disconnecting the indoor blower may trip the inducer limit.
- Wait for outlet air to reach the maximum temperature on the rating plate.
- Confirm the burners shut off.
- If the burners do not shut off in a reasonable time, shut the furnace off manually and replace the limit switch.
- Test the limit with a meter for continuity once it cools to verify it recloses.
- Remove the blockage from the return air inlet after the test.
If the unit shows an error code, look it up: Trane Furnace codes
Source: Trane installer's manual (AUH1B040A9241A), p. 40. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.