Trane Furnace: Gas supply pressure testing
Gas supply pressure testing on a Trane furnace: Gas line pressure testing and the furnace valve: protect the valve from test pressure above 1/2 psig. Higher than that damages the gas valve.
Applies to: Gas line pressure tests
Common causes of gas supply pressure testing
- Furnace left connected during a test above 1/2 psig
- Individual manual shut-off valve left open on a low pressure test
- Test pressure not matched to isolation method
How to fix gas supply pressure testing: step by step
- For tests above 1/2 psig (3.5 kPa), disconnect the furnace and its shut-off valve from the gas supply.
- For tests at or below 1/2 psig (3.5 kPa), close the furnace's individual manual shut-off valve to isolate it.
- Cap the open line before pressurizing.
- After the test, reconnect and leak check all joints before opening the valve.
If the unit shows an error code, look it up: Trane Furnace codes
Source: Trane 18-CD29D1-11 installer's guide, p. 35. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.