Trane Furnace: Furnace location and clearance check before setting in place
Furnace location and clearance check before setting in place on a Trane furnace: Confirm the site meets the basic location requirements before the furnace is moved into position.
Applies to: UH1/DH1 upflow, downflow and horizontal furnaces
How to fix furnace location and clearance check before setting in place: step by step
- Set the furnace as close to the vent run as practical and near the centre of the heat distribution.
- Check that every clearance to the enclosure meets or exceeds the minimums in Table 1 of the manual.
- Leave at least 24 in of front access for service, and make sure any access door or panel can pass the largest component.
- Keep at least 3 in between the furnace front panel and any closed door or panel.
- Keep combustion and ventilation openings unobstructed. For outside air, set the openings at least 12 in above the highest snow level.
- Leave height in the supply plenum for a cooling coil if the coil is not yet installed.
- Protect electrical components from water.
- In a residential garage, mount burners and ignition at least 18 in above the floor and protect the unit from vehicle damage.
- Set the furnace level. Only a slight lean left or forward (upflow) or slight forward lean (horizontal) is allowed, for condensate drainage.
If the unit shows an error code, look it up: Trane Furnace codes
Models
DH1B040A9241DH1B065A9421DH1C085A9481DH1D110A9601UC1B060CUH1C080A9601UH1C100A9481UH1D100A9601UH1D120A9601
Source: Trane installer's guide 18-CD29D1-11, p. 8. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.