Trane Furnace: Freeze protection and drain pipe sizing
Freeze protection and drain pipe sizing on a Trane furnace: Frozen condensate lines block drains and shut the furnace down. Freeze protection and pipe size rules apply.
Applies to: All condensate drain piping
Common causes of freeze protection and drain pipe sizing
- Condensate drain line installed in an unconditioned space
How to fix freeze protection and drain pipe sizing: step by step
- Use 1/2 in or larger PVC or CPVC pipe and fittings for drain connections.
- Use a corrosion-resistant condensate pump if the system needs one.
- If the drain runs in an unconditioned space, apply UL-listed heat tape rated 5 or 6 watts per foot at 120 V, self-regulating preferred, and install per the heat tape maker's instructions.
- Where manifolded with evaporator drains, run a primary drain vent stack that ends below the secondary heat exchanger drain outlet.
- If the furnace is over a finished ceiling, route the stack overflow into an auxiliary drain pan.
If the unit shows an error code, look it up: Trane Furnace codes
Models
UH1B040A9241AUH1B060A9361AUH1B080A9421BUH1C080A9601AUH1C100A9481AUH1D100A9601AUH1D120A9601A
Source: Trane installer's guide, p. 28. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.