Trane Furnace: Filter placement for upflow furnace in horizontal configuration
Filter placement for upflow furnace in horizontal configuration on a Trane furnace: Before you lay an upflow Trane furnace on its side, think about the filter first. The manual says a filter must never sit inside or outside the cabinet directly above the blower assembly in a horizontal setup. Confirm where the return and filter will end up before the unit is set.
Applies to: Upflow furnace in horizontal configuration
Common causes of filter placement for upflow furnace in horizontal configuration
- Filter placed directly above the blower in a horizontal install
- No remote filter or upstream filter provision in the ductwork
- Wrong conversion kit for the cabinet width
How to fix filter placement for upflow furnace in horizontal configuration: step by step
- Do not place the filter directly above the blower, inside or outside the cabinet.
- Use a remote filter grille, or install the filter in the ductwork upstream of the furnace.
- For conversion, use filter kit BAYFLTR203 (17.5 in cabinet), BAYFLTR204 (21 in) or BAYFLTR205 (24.5 in). These include the filters and brackets needed for horizontal filters.
- Match the kit to your cabinet width before ordering.
- After installation, confirm the filter is seated and no air bypasses it.
If the unit shows an error code, look it up: Trane Furnace codes
Source: Trane AUH1B080A9421B installer's manual, p. 17. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.