Trane Furnace: Condensate drain for vertical upflow and downflow installations
Condensate drain for vertical upflow and downflow installations on a Trane furnace: Upflow and downflow units use different drain tubing and trap routing, and the drain should have a drain pan under it.
Applies to: Upflow and downflow vertical installations
How to fix condensate drain for vertical upflow and downflow installations: step by step
- Install a drain pan under the furnace to prevent leak damage.
- Upflow: find the drain tubing for left and right side drainage in the blower compartment. Run it from the trap to the side of the unit, and trim excess to avoid kinks.
- Upflow: use the 2 in to 3 in reducing coupling marked TOP, with the TOP mark on the top side of the pipe and the straight side on the bottom.
- Downflow: seal the fitting to the trap with RTV silicone so the trap can be removed for cleaning.
- Downflow left side: use a 1/2 in slip PVC fitting.
- Downflow right side: remove the drain lines, rotate the trap 180 degrees, and reconnect. Use a 1/2 in 90 degree CPVC street elbow sealed with RTV, 1/2 in CPVC to an elbow, then 1/2 in CPVC out through the right side knockout.
If the unit shows an error code, look it up: Trane Furnace codes
Models
UH1B040A9241AUH1B060A9361AUH1B080A9421BUH1C080A9601AUH1C100A9481AUH1D100A9601AUH1D120A9601A
Source: Trane installer's guide, p. 26. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.