Trane Furnace: Carbon monoxide spillage test (vent check)
Carbon monoxide spillage test (vent check) on a Trane furnace: Run before returning a furnace to service on a shared vent. Failure to follow this can cause carbon monoxide poisoning or death.
Applies to: Draft hood appliances on a shared vent
How to fix carbon monoxide spillage test (vent check): step by step
- Seal any unused openings in the venting system.
- Check the venting system for proper size, horizontal pitch, blockage, restriction, leakage and corrosion, per NFPA 54 / CSA B149.1.
- Close building doors and windows and the doors between the space and the other appliances.
- Close fireplace dampers.
- Turn on clothes dryers and any appliance not on the vent. Run exhaust fans such as range hoods and bathroom exhausts at maximum speed. Do not run a summer exhaust fan.
- Light the appliance under test and set the thermostat so it runs continuously.
- After 5 minutes of main burner operation, test for spillage at the draft hood relief opening with a match or candle.
- If spillage shows, correct the venting to code before continuing.
- Return doors, windows, fans, dampers and other appliances to their previous condition.
If the unit shows an error code, look it up: Trane Furnace codes
More service & test modes tips for furnace
Source: Trane AUH1B080A9421B installer's manual, p. 18. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.