Updated · by Aurora Star Tech Inc.

Natural gas at high altitude: derate on a Rheem furnace: No high altitude pressure switch changes are needed. Derate the input by 4% per thousand feet above 2,000 ft. Factory orifices are sized for 1100 BTU/ft3 at sea level; regional heating values may remove the need to change them except at extreme altitudes. Above 2,000 ft, follow local codes or NFGC/CSA B149.1.

Homeowner with a furnace problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Natural gas above 2,000 ft

How to fix natural gas at high altitude: derate: step by step

  1. Derate the input 4% per 1,000 ft above 2,000 ft.
  2. Check the local gas heating value before changing orifices.
  3. Follow local codes, or NFGC / CSA B149.1 where no local code applies.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Rheem Furnace codes

Models

96V

(-)96V060(-)96V070(-)96V085(-)96V10096VA06096VA07096VA08596VA100

96MDV

96MDV06096MDV07096MDV08596MDV100

More other tips for furnace

Source: 96V series installation instructions, p. 80. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.