Rheem Furnace: Measuring and adjusting manifold gas pressure
Measuring and adjusting manifold gas pressure on a Rheem furnace: Manifold pressure is the pressure at the gas valve outlet that actually feeds the burners. I check it with a heat call active, and I set it on high fire first. If the flame looks wrong or the furnace is over or under fired, this is where you look right after you have confirmed supply pressure is good. Take it slow when you turn the regulator screw, because small turns move the number a lot. Gas work is for the licensed tech.
Applies to: Gas valve outlet pressure
Common causes of measuring and adjusting manifold gas pressure
- Flame is lazy, yellow or lifting from the burners
- Furnace is over or under fired after a conversion or altitude change
- Regulator out of adjustment
- Supply pressure not within limits
How to fix measuring and adjusting manifold gas pressure: step by step
- Shut off gas at the manual gas valve and remove the outlet pressure tap plug
- Loosen (do not remove) the outlet tap screw with a 3/32 allen wrench
- Connect the manometer with 5/16 in. I.D. hose
- Turn gas on and apply a heat call
- Set manifold pressure to 3.5 in. w.c. (natural gas) or 10.0 in. w.c. (LP) on high fire
- Remove the regulator cap and turn the adjustment screw to set the pressure
- Replace the regulator cap securely
- Shut off gas, remove manometer and hose, and tighten the inlet tap screw
- Turn gas on, apply a heat call and check for leaks with an approved detector
If the unit shows an error code, look it up: Rheem Furnace codes
Models
96V
(-)96V060(-)96V070(-)96V085(-)96V10096VA06096VA07096VA08596VA100
96MDV
96MDV06096MDV07096MDV08596MDV100
Source: 96V series installation instructions, p. 75. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.