Rheem Furnace: Canada only: derate high altitude by lowering manifold pressure
Canada only: derate high altitude by lowering manifold pressure on a Rheem furnace: In Canada, unless local codes mandate an orifice change, altitude derate can be done by lowering manifold pressure instead. The table values assume 1000 BTU per cu ft natural gas and 2500 BTU per cu ft LP. The actual input must be measured on site to confirm a real 10 percent reduction.
Applies to: 90 Plus models, Canadian installations 2,000 to 4,500 ft
How to fix canada only: derate high altitude by lowering manifold pressure: step by step
- Confirm the installation is in Canada and that local codes do not require an orifice change.
- Find the altitude band and fuel type in the alternate derate table.
- Set the manifold pressure to the value shown for that band.
- Measure the actual input rate on site and confirm about a 10 percent reduction.
- Attach the manifold pressure change label (Figure 43, part 92-24399-01-01) to the front of the furnace cabinet in a visible spot.
If the unit shows an error code, look it up: Rheem Furnace codes
Models
96V
(-)96V060(-)96V070(-)96V085(-)96V10096VA06096VA07096VA08596VA100
96MDV
96MDV06096MDV07096MDV08596MDV100
Source: Rheem 96V series installation instructions, p. 82. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.