Icon
Reliable Heating and Cooling Solutions – Quality Service, Fair Prices, Guaranteed Satisfaction!

Goodman Furnace: Loss of communication with circulator blower motor

Updated · by Aurora Star Tech Inc.

Loss of communication with circulator blower motor on a Goodman furnace: The integrated control module and the circulator motor have stopped talking to each other, and the furnace won't run. What I usually find is a plug that's backed out or a loose control lead, so start there before you condemn the motor. Motor and board both fail occasionally, but wiring comes first.

Homeowner with a furnace problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: 34.5 in chassis gas furnaces

Common causes of loss of communication with circulator blower motor

  • Loose wiring at the circulator motor control leads
  • Failed circulator blower motor
  • Failed integrated control module

How to fix loss of communication with circulator blower motor: step by step

  1. Turn power off before repair.
  2. Reseat and tighten the motor control lead connections and look for pins that are pushed back or corroded.
  3. Tighten or correct the wiring connection wherever you find a fault.
  4. Check the circulator blower motor and replace it if needed.
  5. Check the integrated control module and replace it if needed, once wiring and motor are cleared.
  6. Restore power and watch for communication on a call for heat.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Goodman Furnace codes

Source: Goodman GMVC96 Service and Troubleshooting, p. 63. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.

Emergency Furnace Repair

647-657-2977