Rinnai Wall Furnace: Set low and high fire gas pressure with the Test Switch
Set low and high fire gas pressure with the Test Switch on a Rinnai wall furnace: PL is the low-fire setting screen and PH the high-fire one; adjust with the up and down buttons against the manometer.
Applies to: Rinnai EX08DT, EX11DT, EX17DT, EX22DT direct vent wall furnaces
How to fix set low and high fire gas pressure with the test switch: step by step
- In the gas pressure setting procedure, press the Test Switch twice while the furnace is on: PL shows.
- Compare the manometer reading with the table for the gas, altitude and vent length; adjust with the up and down buttons.
- Press the Test Switch to move to PH.
- Compare the manometer reading with the table; adjust with the up and down buttons.
- Press ON/OFF to finish; the display goes blank and the furnace returns to normal off mode.
If the unit shows an error code, look it up: Rinnai Wall Furnace codes
Models
EX08DTEX11DTEX17DTEX22DTEX22DT-W
More service & test modes tips for wall furnace
Source: Rinnai EX08DT/EX11DT Installation and Operation Manual (200000083) and EX17DT/EX22DT (200000084), Gas pressure setting steps 10-11 p.26. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.