Gree Heat Pump: Read live running parameters of an outdoor module (function n7)
Read live running parameters of an outdoor module (function n7) on a Gree heat pump: Shows parameter codes such as outdoor ambient, compressor frequency and pressures for a chosen module.
Applies to: Gree GMV6 Ultra Heat Mini VRF 36-60k (GMV-V..WL/C-T(U))
How to fix read live running parameters of an outdoor module (function n7): step by step
- Hold SW2 on the master for over 5 seconds, select n7 and confirm with SW3.
- Pick the module with SW1 and SW2 and confirm with SW3.
- Pick the parameter code with SW1 and SW2.
- Four-digit temperatures show as two pairs, for example 01 then 15 for 115 degrees; a negative reading is introduced by nE.
If the unit shows an error code, look it up: Gree Heat Pump codes
Models
GMV-V36WL/C-T(U)GMV-V48WL/C-T(U)GMV-V60WL/C-T(U)
Source: Gree GMV6 Ultra Heat Mini VRF 36-60k (GMV-V36-48-60WL-C-T(U)) service.pdf - section 4.2.4.2 and Chapter 3 Faults, 4.1 Error Indication. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.