Rheem Furnace: Blower codes 66, 61 and 60 – what to look for
Blower codes 66, 61 and 60 - what to look for on a Rheem furnace: Quick sorting of the three ECM motor codes on the R96V control.
Applies to: (-)96VA040-115 (R96V / U96V) and (-)(-)96MDV040-115 two-stage variable-speed communicating furnaces
Common causes of blower codes 66, 61 and 60 - what to look for
- Restricted or confined ductwork, closed registers (66)
- Loose motor set screw (66)
- Blocked wheel, locked rotor or overheating motor (61)
- Minor internal motor fault (60)
How to fix blower codes 66, 61 and 60 - what to look for: step by step
- 66 (overspeed / power limit) only shows in the first three minutes of blower operation: open registers, remove duct restrictions, and check the motor set screw is tight on the shaft.
- 61 (motor cannot run): clear any obstruction from the wheel and find the cause of overheating; if it keeps failing the motor is likely damaged and needs replacing. Four dead-blower events in one heat call put the control in hard lockout.
- 60 (motor able to run): low-level fault, operation continues; no long-term damage expected.
- Static pressure should never exceed 1.0 in. w.c. on this ECM furnace.
If the unit shows an error code, look it up: Rheem Furnace codes
Models
96MDV040B30A96MDV060B30A96MDV070B30A96MDV085C50A96MDV100C50A96MDV115D50AR96VA0401317MSAR96VA0601317MSAR96VA0701317MSAR96VA0851521MSAR96VA1001521MSAR96VA1151524MSA
Source: Rheem (-)96V / (-)(-)96MDV Installation Instructions 92-24161-124-08, Diagnosing blower motor issues p.123. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.