York Furnace: Read or clear stored fault codes with the LAST ERROR button
Read or clear stored fault codes with the LAST ERROR button on a York furnace: The board keeps up to five fault codes, newest first, through power loss. Solid-LED errors are not stored. Retrieval only works with no thermostat signal active.
Applies to: York IFC boards with LAST ERROR button
How to fix read or clear stored fault codes with the last error button: step by step
- End any heating, cooling or continuous-fan call
- Press and release LAST ERROR (more than 1/5 s, under 5 s); the LED flashes the stored codes, most recent first, with a 2 second pause between
- TM9V: after the codes it returns to slow green flash after a 5 second pause; press again to repeat
- Two green flashes = nothing stored
- To clear, hold the button 5 seconds or more; three green flashes confirm
If the unit shows an error code, look it up: York Furnace codes
Models
TM9V040A10TM9V060B12TM9V080B12TM9V080C16TM9V100C16TM9V100C20TM9V120D20
More service & test modes tips for furnace
Source: York service letter ST-028-07 White Rodgers/Emerson IFC boards, Fault Code Sheet, p.5-7; York service tip ST-045-09 UTEC IFC boards, Fault Code Sheet; York TM9V installation manual 1083294-UIM-A-0114, Fault Code Storage and Retrieval, p.42. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.