Weil-McLain Heat Pump: Water chemistry and Sentinel X100 inhibitor
Water chemistry and Sentinel X100 inhibitor on a Weil-McLain heat pump: Sentinel X100 is required for the ECO HP to protect its heat exchanger. Check water chemistry after filling.
Applies to: ECO HP split air-to-water heat pump
Common causes of water chemistry and sentinel x100 inhibitor
- Water outside pH 7.0-8.5 or with too little inhibitor can cause corrosion.
- Chloride above 100 ppm is not allowed in the heat pump.
How to fix water chemistry and sentinel x100 inhibitor: step by step
- Fill the system, then add X100 aerosol as the container directs.
- Let the water circulate, then check the inhibitor level with the Sentinel test kit. Add more if needed.
- Test the water pH at least once a year. It must be between 7.0 and 8.5.
- If pH is out of range, consult a local water treatment company.
- Verify chloride is below 100 ppm before filling.
- Do not use the heat pump to heat swimming pool or spa water.
- Check antifreeze concentration at least once a year if antifreeze is used.
If the unit shows an error code, look it up: Weil-McLain Heat Pump codes
Source: ECO HP Heat Pump Application Guide, pp. 60-61. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.