Weil-McLain Heat Pump: Verify thermostat circuits (external wiring check)
Verify thermostat circuits (external wiring check) on a Weil-McLain heat pump: Confirm no voltage is fed back into the boiler control module from external devices.
Applies to: ECO HP with boiler and thermostat inputs
Common causes of verify thermostat circuits (external wiring check)
- Voltage feeding back from external wiring can damage the control module.
- Connecting thermostat terminals to 3-wire zone valves can damage the control.
How to fix verify thermostat circuits (external wiring check): step by step
- Mark the wires on the thermostat inputs of the control board (Unity 2.0 board for Type A, DHW-priority zone panel for Types B and C).
- Disconnect the external thermostat circuit wires.
- Close each thermostat, zone valve or relay one at a time. Measure voltage from each wire to ground.
- There should never be a voltage reading when an external device is closed.
- If voltage is found, correct the external wiring.
- Do not connect thermostat terminals to 3-wire zone valves.
- Reconnect the thermostat wires after the check.
If the unit shows an error code, look it up: Weil-McLain Heat Pump codes
Source: ECO HP Heat Pump Application Guide, p. 61. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.