Weil-McLain Heat Pump: Verify flow rate through the ECO HP
Verify flow rate through the ECO HP on a Weil-McLain heat pump: Confirm the heat pump has enough flow before running it. It will not operate below 3.1 GPM.
Applies to: ECO HP split air-to-water heat pump
Common causes of verify flow rate through the eco hp
- Closed or partly closed zones reduce flow below the minimum.
- A strainer that is plugged or air in the system reduces flow.
How to fix verify flow rate through the eco hp: step by step
- Find which space heating loops can be closed by mechanical, electronic or other valves.
- Close all space heating loops that can be closed.
- Start the circulation pump. Use the Test run menu and Point check menu in the For Serviceman menu to run Pump_i manually.
- Read the flow and adjust until it is between 6 and 10 GPM.
- With the Easy-Up Manifold, set the circulator speed dial to MAX for about 7-12 GPM, then use ECOCalc to fine-tune.
If the unit shows an error code, look it up: Weil-McLain Heat Pump codes
Source: ECO HP Heat Pump Application Guide, p. 61. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.