Weil-McLain Heat Pump: Unit on but not heating or cooling as expected
Unit on but not heating or cooling as expected on a Weil-McLain heat pump: Unit runs but the water temperature does not get where it should.
Applies to: ECO HP 41/48/55 MBH indoor unit / hydro-box (IDU)
Common causes of unit on but not heating or cooling as expected
- Temperature limits set wrong
- Water flow too low
- Too little water in the system
How to fix unit on but not heating or cooling as expected: step by step
- Check the T4 limit parameters for the mode: T4HMAX/T4HMIN (heat), T4CMAX/T4CMIN (cool), T4DHWMAX/T4DHWMIN (DHW).
- Check every shut-off valve is open and the strainer is clean.
- Purge air. Check the gauge: cold water pressure must be over 14.5 psi.
- Check the expansion tank and that the pipe system is not too restrictive for the pump.
- Confirm system water volume is above the minimum (manual section 8.5.2).
If the unit shows an error code, look it up: Weil-McLain Heat Pump codes
Models
Source: Weil-McLain ECO HP Split Air-to-Water Heat Pump IDU Product Manual 550-100-586/0824, sec. 11.2 General symptoms, p.53. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.