Weil-McLain Heat Pump: System Type C control connections (ECO HP solo)
System Type C control connections (ECO HP solo) on a Weil-McLain heat pump: Type C uses only the ECO HP with no other heat source. Calls for heat or DHW go through a DHW-priority zone panel such as the TIU, and its end switches feed the heat pump inputs. The heat pump only connects directly to dry contacts rated 12 Vdc. Only one zone circulator is supported natively.
Applies to: System Type C, ECO HP solo and Multi-HP
How to fix system type c control connections (eco hp solo): step by step
- Route the heat or DHW call through the TIU end switches to the heat pump inputs.
- Use only 12 Vdc rated dry contacts for direct connections to the heat pump.
- If priority of circulators or zone valves is needed, use a DHW-priority zone panel with priority functionality, such as the TIU.
- Let the heat pump run its own circulator; it can also control one space heat zone circulator.
- For a DHW circulator, add an isolation relay.
- Use the TIU to control any additional circulators.
- Zone valve systems can be wired from the valve dry contacts straight to the indoor unit, unless priority zone valve control is needed.
If the unit shows an error code, look it up: Weil-McLain Heat Pump codes
Source: ECO HP Heat Pump - Application Guide, p. 42. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.