System Type B, Application B1 piping layout on a Weil-McLain heat pump: Boiler direct piped with an indirect DHW heater, multi-zone space heating and DHW as a zone. Heat pump, boiler, manifold and zone parts are shown in the piping figure. Items marked as supplied with the boiler or heat pump come with the unit. All others are supplied by the installer.
Applies to: System Type B, Application B1 (boiler direct piped, DHW as zone)
How to fix system type b, application b1 piping layout: step by step
- Set up the easy-up or field-fabricated manifold for the heat pump and boiler.
- Install a relief valve on the boiler and on the heat pump and pipe each relief valve to drain.
- Fit isolation valves, a Y-strainer with 80 mesh screen, and an expansion tank.
- Install an air separator and purge/drain valves at the points shown.
- Install flow/check or spring check valves and a heat trap where the figure shows them.
- Pipe the DHW circulator, DHW temperature and pressure relief valve, and the indirect water heater if used.
- Pipe zone circulators and zone valves, and fit a bypass pressure regulator.
- Keep piping within the spacing shown in the figure (do not exceed 8 pipe diameters apart).
- Install unions where needed for service and add a make-up water supply.
If the unit shows an error code, look it up: Weil-McLain Heat Pump codes
Source: ECO HP Heat Pump Application Guide, p. 25. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.