Warming things up…Dialing in your comfort…Almost cozy…
Reliable Heating and Cooling Solutions – Quality Service, Fair Prices, Guaranteed Satisfaction!

Weil-McLain Heat Pump: System Type A, Application A1: multi-zone heating with DHW as a zone – piping layout

Updated · by Aurora Star Tech Inc.

System Type A, Application A1: multi-zone heating with DHW as a zone – piping layout on a Weil-McLain heat pump: Primary/secondary piping is required. With a Unity 2.0 boiler, the boiler must sit downstream of the ECO HP so that high boiler water temperatures do not reach the heat pump inlet. The DHW zone is fed through an indirect tank and needs a circulator sized for the tank and piping pressure drop. Large indirect tanks may need different piping for the required flow. Zone circulators must be sized for flow and are supplied by the installer. The heat pump circulator is in the heat pump manifold. ECO Tec boilers have an internal boiler circulator.

Homeowner with a heat pump problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: System Type A, Application A1 (Unity 2.0 boiler with ECO HP)

How to fix system type a, application a1: multi-zone heating with dhw as a zone – piping layout: step by step

  1. Pipe the system primary/secondary.
  2. Place the boiler downstream of the ECO HP when both run together.
  3. Size the DHW circulator for the indirect tank and piping pressure drop.
  4. Size each space heating zone circulator for its zone flow.
  5. Confirm the heat pump circulator is installed in the heat pump manifold.
  6. Use a DHW-priority zone panel such as the Weil-McLain Thermostat Interface Unit if alternate wiring is needed.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Weil-McLain Heat Pump codes

Source: ECO HP Heat Pump – Application Guide, p. 16. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.

Emergency HVAC Service

647-657-2977