Weil-McLain Heat Pump: Pump noisy (cavitation)
Pump noisy (cavitation) on a Weil-McLain heat pump: Pump makes a gravel-like noise.
Applies to: ECO HP 41/48/55 MBH indoor unit / hydro-box (IDU)
Common causes of pump noisy (cavitation)
- Air in the system
- Pump inlet pressure too low
How to fix pump noisy (cavitation): step by step
- Purge air.
- Check the gauge: cold water pressure must be over 14.5 psi, and the gauge itself must work.
- Check the expansion tank and its pre-charge (manual section 8.5.2).
If the unit shows an error code, look it up: Weil-McLain Heat Pump codes
Models
Source: Weil-McLain ECO HP Split Air-to-Water Heat Pump IDU Product Manual 550-100-586/0824, sec. 11.2 General symptoms, p.54. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.