Weil-McLain Heat Pump: Pump making noise (cavitation)
Pump making noise (cavitation) on a Weil-McLain heat pump: The pump is cavitating, usually from air or low inlet pressure.
Applies to: ECO HP heat pump
Common causes of pump making noise (cavitation)
- Air in the system
- Water pressure at pump inlet too low
- Pressure and temperature gauge broken
- Expansion vessel broken or pre-pressure set incorrectly
How to fix pump making noise (cavitation): step by step
- Purge air from the system.
- Check the gauge for sufficient water pressure; must be above 14.5 psi with cold water.
- Check that the pressure and temperature gauge is not broken.
- Check that the expansion vessel is not broken.
- Check that the expansion vessel pre-pressure setting is correct.
If the unit shows an error code, look it up: Weil-McLain Heat Pump codes
Source: ECO HP Heat Pump – Application Guide, p. 65. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.