Weil-McLain Heat Pump: General troubleshooting checks before diagnosing codes
General troubleshooting checks before diagnosing codes on a Weil-McLain heat pump: Do a visual inspection first. Shut off power before opening internal components.
Applies to: ECO HP split air-to-water heat pump
Common causes of general troubleshooting checks before diagnosing codes
- Loose connections or defective wiring.
- Blown fuses or a safety device that has tripped.
- Faulty temperature sensors.
How to fix general troubleshooting checks before diagnosing codes: step by step
- Check the error and lockout histories and read the most recent items.
- Use a voltmeter to confirm 120 Vac to the boiler and the HP indoor unit, and 240 Vac to the heat pump outdoor unit.
- Confirm the thermostat is calling for heat and 24 Vac is present between thermostat wires and ground.
- Confirm no safety device has tripped. Find the cause before resetting it. Never bridge safety devices or change them from factory settings.
- Confirm all control connectors are fully seated.
- Replace any blown fuses.
- Check temperature sensors against known temperatures and their resistance readings.
- If a pressure relief valve is replaced, reconnect its drain piping.
If the unit shows an error code, look it up: Weil-McLain Heat Pump codes
Source: ECO HP Heat Pump Application Guide, p. 62. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.