Weil-McLain Heat Pump: Freeze protection and antifreeze dosing
Freeze protection and antifreeze dosing on a Weil-McLain heat pump: Use only antifreeze listed by WM Technologies for the ECO HP. Never exceed 50% by volume.
Applies to: ECO HP split air-to-water heat pump
Common causes of freeze protection and antifreeze dosing
- Antifreeze that is too strong slows heat transfer and can form sludge in the heat pump.
- Glycol and inhibitor levels drop over time and can leak out before water does.
How to fix freeze protection and antifreeze dosing: step by step
- Flush any system that has used glycol before installing the heat pump.
- Check the antifreeze and inhibitor levels at least once a year.
- If using automatic fill with antifreeze, install a water meter to watch make-up water.
- Find the concentration needed for the lowest likely temperature from the antifreeze container data.
- Add up the system volume, including the expansion tank and the heat pump (0.41 gal).
- Multiply the total volume by the required percentage to get gallons of antifreeze.
If the unit shows an error code, look it up: Weil-McLain Heat Pump codes
Source: ECO HP Heat Pump Application Guide, pp. 59-60. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.