Weil-McLain Heat Pump: Fill, test and purge air from the water system
Fill, test and purge air from the water system on a Weil-McLain heat pump: Fill only after the water meets the manual's requirements. Eliminate all leaks, because make-up water shortens heat pump and boiler life.
Applies to: ECO HP split air-to-water heat pump
Common causes of fill, test and purge air from the water system
- Trapped air restricts flow and can trigger the water flow failure codes.
How to fix fill, test and purge air from the water system: step by step
- Close the manual and automatic air vents and the heat pump drain valve.
- Fill to the correct cold-fill pressure for the application (typically 12 psi residential).
- Check for leaks at fill and during startup. Repair all leaks before continuing.
- Connect a hose to the system purge valve and route it to a drain you can see.
- Close the heat pump or system isolation valve between the purge valve and the fill connection.
- Close zone isolation valves. Open the quick-fill valve and the purge valve.
- Open one zone isolation valve at a time and purge until no air flow shows. Close it and move to the next zone.
- Purge the boiler and its internal piping the same way.
- Close the quick-fill and purge valves, remove the hose and open all isolation valves.
- Bleed remaining air at manual vents, starting at the lowest floor. Open the automatic air vent one turn if the system has one.
- Refill to the correct pressure. Operating pressure must never exceed 24 psi.
If the unit shows an error code, look it up: Weil-McLain Heat Pump codes
Source: ECO HP Heat Pump Application Guide, p. 60. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.