Weil-McLain Heat Pump: Blank display at first start-up
Blank display at first start-up on a Weil-McLain heat pump: Nothing shows on the user interface on a new install.
Applies to: ECO HP 41/48/55 MBH indoor unit / hydro-box (IDU)
Common causes of blank display at first start-up
- Wiring missing or wrong between power supply and unit, or unit and user interface
- PCB fuse blown
- E8/E0 at start-up: air in the system or water level too low
- E2 at start-up: user interface wiring
How to fix blank display at first start-up: step by step
- Turn off power at the disconnect before opening the unit or touching any wiring.
- Check power wiring to the unit and the wire to the user interface.
- Check the PCB fuse.
- E8 or E0 on start-up: purge air and fill the system to the minimum level.
- E2: check the wiring between the user interface and the unit.
If the unit shows an error code, look it up: Weil-McLain Heat Pump codes
Models
Source: Weil-McLain ECO HP IDU Product Manual 550-100-586/0824, Failure diagnosis at first installation, p.42. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.