Weil-McLain Heat Pump: Application C2 circulators and primary/secondary piping
Application C2 circulators and primary/secondary piping on a Weil-McLain heat pump: Multi-zone space heating with zone valves. Piping must be primary/secondary. The heat pump circulator sits in the heat pump manifold.
Applies to: Application C2 multi-zone space heating
How to fix application c2 circulators and primary/secondary piping: step by step
- Pipe the system as primary/secondary.
- Size the system circulator for the required head.
- Check the system circulator current draw.
- If the system circulator draws more than 0.2A, install an isolation relay.
- Confirm the heat pump circulator is installed in the heat pump manifold (included in the heat pump accessory box).
If the unit shows an error code, look it up: Weil-McLain Heat Pump codes
Source: ECO HP Heat Pump Application Guide, p. 50. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.