Weil-McLain Heat Pump: Application B2 piping layout
Application B2 piping layout on a Weil-McLain heat pump: Primary/secondary piping for two space heating zones and a DHW zone, with a boiler circulator and heat pump circulator in the manifold.
Applies to: System Type B, Application B2
How to fix application b2 piping layout: step by step
- Set up the easy-up or field-fabricated manifold for the heat pump and boiler.
- Install the boiler circulator (shipped loose with the boiler) on the boiler piping.
- Install the heat pump circulator (in the heat pump manifold) with its internal flow check valve.
- Install relief valves on the boiler and heat pump and pipe them to drain.
- Install isolation valves, Y-strainer with 80 mesh screen, expansion tank, air separator and purge/drain valves.
- Install zone valves and zone circulators, and the DHW circulator with DHW temperature and pressure relief valve.
- Keep piping within the spacing shown (do not exceed 8 pipe diameters apart).
- Install unions where needed for service and add a make-up water supply.
If the unit shows an error code, look it up: Weil-McLain Heat Pump codes
Source: ECO HP Heat Pump Application Guide, p. 31. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.