Weil-McLain Combi Boiler: Wrong boiler model shown at power-up
Wrong boiler model shown at power-up on a Weil-McLain combi boiler: The power-up screen shows the boiler model set in the control. If it does not match the rating plate, the boiler can run unsafely.
Applies to: ECO Tec 110C, 150C, 199C Series 3 (combi)
Common causes of wrong boiler model shown at power-up
- Wrong model picked during setup
- Control replaced or reset to factory defaults
- Blower type on a 199/199C does not match the blower installed
How to fix wrong boiler model shown at power-up: step by step
- Turn the boiler off if the model is wrong.
- Compare with the model on the rating plate.
- Change it in contractor menu > Boiler Settings > Boiler Model. Choices: ECO Tec 80, 110, 110 Combi, 150, 150 Combi, 199, 199 Combi.
- On 199 and 199C you also pick the blower type (EF90 or NG150). Read the blower label and pick the same one.
- Changing the model or blower type resets all boiler settings, so go through the setup again after.
- Also check Altitude (set it if the site is above 2,000 ft, in 500 ft steps) and Fuel Type.
Source: Weil-McLain ECO Tec Series 3 Advanced Manual 550-100-600/1025, sec. Control action - Power up, p.3; Boiler Settings, p.58. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.