Weil-McLain Combi Boiler: ECO Tec S2 will not light after gas conversion
ECO Tec S2 will not light after gas conversion on a Weil-McLain combi boiler: Coarse gas valve settings get the boiler to light. Final set-up must be done with a combustion analyzer in Manual Test Mode.
Applies to: ECO Tec 110/150/199 Series 2 combi
Common causes of eco tec s2 will not light after gas conversion
- Throttle or offset screw not set to the coarse position
- Fuel type in the control does not match the gas
- Max or min rate set wrong
How to fix eco tec s2 will not light after gas conversion: step by step
- Gas qualified tech only. Use a calibrated flue gas analyzer.
- Make sure Fuel Type in Boiler Settings matches the gas (propane or natural gas).
- Propane coarse settings (throttle turns CCW from bottomed out): 80/110 = 6-3/4, 150 = 10-3/4, 199 = 13. Offset from the factory NG mark: 80/110 = 1/8 turn CCW, 150 and 199 = 0.
- Natural gas coarse throttle turns: 80/110 = 9-1/8; 150 and 199 per Figure 22 (text reads 12 and 14-1/2, check the page).
- Bottom out the throttle screw gently. Never bottom out the offset screw.
- Still will not light: turn the throttle CCW 1/4 turn more and try again, up to one full extra turn. Still no light, or O2 under 1.0%: call Weil-McLain tech support.
- Before firing, Max Rate should be 96 to 100% and Min Rate 10%.
- Set high fire with the throttle screw, then low fire with the offset screw, to the CO2/CO ranges on p.125. Do not let it modulate until combustion is set.
Source: Weil-McLain ECO Tec Series 2 Boiler Manual 550-100-270/0924, Gas conversions p.17-18. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.