Weil-McLain Combi Boiler: ECO Tec S2 condensate line blocked or frozen
ECO Tec S2 condensate line blocked or frozen on a Weil-McLain combi boiler: If condensate cannot drain, it can come out of the boiler tee and cause water damage.
Applies to: ECO Tec 110/150/199 Series 2 combi
Common causes of eco tec s2 condensate line blocked or frozen
- Frozen or blocked drain line
- Condensate pump too small or failed
How to fix eco tec s2 condensate line blocked or frozen: step by step
- Check the drain line is clear and protected from freezing.
- Condensate pump minimum capacity: 2 GPH (80), 3 GPH (110), 4 GPH (150), 5 GPH (199), plus any other appliances on the same pump. The pump should have an overflow switch.
- Condensate is acidic (pH about 3.2 to 4.5). Use a neutralizer when draining to metal pipe or where code requires.
Source: Weil-McLain ECO Tec Series 2 Boiler Manual 550-100-270/0924, Condensate drain p.57. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.